Customization: | Available |
---|---|
After-sales Service: | 3 Years |
Warranty: | 3 Years |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
AT-MPM-S uses a 96mm panel mounted display and can be used in conjunction with our new "MultiClick" solution. It allows you to monitor 32 three-phase / 96 single-phase channels from a centralized point, eliminating the need for 32 separate panel meters. All MPM devices connected to the MPM bus can be configured through the human-machine interface. The series products are connected via RJ, without manual twisting of wires, saving construction time, facilitating installation, and being safe and reliable.
Voltage/Current Input | Rated Voltage | L230 VAC(L-N)/400 VAC(L-L) | ||
CT Input | 100mV | |||
Voltage Input | Measurement Range:85~276 VAC(L-N),85~480 VAC(L-L) | |||
Frequency | 45~65 Hz | |||
Overload Capacity | 2xRated Voltage by lasting 1s | |||
IP Class | LCD display:IP51(Indoor); | |||
Installation | TH35-7.iDIN Rail | |||
Flammability Class | UL 94 V-0 | |||
Utilization Category | UC2 | |||
Environment Specifications | Operation Temperature | -25~+55ºC | ||
Storage Temperature | -40~+80ºC | |||
Humidity | <90%,no condensing | |||
Vibration Frequency | Range:10~150Hz,Refer to IEC 60068-2-6 | |||
Communication Specifications | Interface and Protocol | 2-Wire RS485;Modbus RTU | ||
Baudrate | 1200,2400,4800,9600(Default),19200,38400 bps | |||
Parity | None(Default),Even,Odd | |||
Stop Bit | 1(Default),2 | |||
Response Time | <100ms | |||
Communication Terminals | Wire Diameter:26~14 AWG;Torque:0.4 N.m(Max.) | |||
Temperature Rating of Connection Cable | 23ºC±2ºC |