Working Power |
|
Operating range |
AC/DC85~265V
|
Power consumption |
≤5W |
AC input |
|
Input voltage Rated |
AC 100V,220V,400V |
Overload |
1.2times continuous,2times( 10s) |
Power consumption |
<0.4VA/phase |
Impedance |
≥200kΩ |
Primary current |
1-9999A |
Secondary input |
1Aor5A |
Short-time overcurrent |
20 times Max. current for 0.5 s |
Power consumption |
<0.2VAPhase |
Impedance |
≥0.1Ω |
Input-output |
|
Switch inputs |
Dry contact input, opto-isolated |
Switch outputs |
Relay output; any power alarm can be set, default remote control |
Comm Port |
|
RS4S5 |
Modbus RTUAccuracy |
Accuracy |
|
Voltage/Current |
0.5% |
Frequency |
0.2% |
Power / Power |
1% |
Active power |
Class0.5S |
Reactive power |
Class2 |
Operation Environment |
|
Operating temperature |
-25ºC~55ºC |
Storage temperature |
-40ºC~70ºC |
Operating humidity |
≤90%RH,non-condensing, no corrosive air |
Storage humidity |
≤95%RH,non-condensing, no corrosive air |
Altitude |
≤2000m |
Electromagnetic compatibility Performance |
|
Electrostatic discharge |
Class (GB/T 17626.2 IEC 61000-4-2) |
RF Field Strength |
Class (GB/T 17626.3 IEC 61000-4-3) |
Electrical Fast Transient /Burst Test |
Class (GB/T 17626.4 IEC 61000-4-4) |
Surge Test |
Class IV(GB/T 17626.5 IEC 61000-4-5) |
Conducted Susceptibility Test |
Class (GB/T 17626.6 IEC 61000-4-6) |
Power |
Class (GB/T 17626.8 IEC 61000-4-8) |
Oscillating wave immunity |
Class (GB/T 17626.12 IEC 61000-4-12) |
Electromagnetic emission limits |
Accordant(GB/T 14598.16 IEC 60255-25) |
Overall Dimension |
|
H*W*D |
96mm×96mm×75mm |
Cut-out Dimension | 92mm×92mm |