Measurement accuracy |
Voltage/Current | Class 0.5, reference standard IEC 61557-12 |
Active power | Class 0.5, reference standard IEC 61557-12 | |
Reactive power | Class 2, reference standard IEC 61557-12 | |
Apparent power |
Class 1, reference standard IEC 61557-12 | |
Active power | Class 0.5S, reference standard IEC 62053-21/22, IEC 61557-12 |
|
Reactive power | Class 2, reference standard IEC 62053-23; Class 2, reference standard IEC 61557-12 |
|
Power factor | Class 1, reference standard IEC 61557-12 | |
Frequency | Class 0.2, reference standardIEC 61557-12 | |
Measurement data update rate | 1s(Optional 100ms) |
Measuring the input voltage |
Rated voltage | 230 VAC(Phase voltage) / 400 VAC(Line voltage) |
Direct access | Measurement range: 30~300 VAC(Phase voltage);30~500 VAC(Line voltage) |
|
PT access | Maximum primary side value of PT supported: 500000 VAC |
|
Measuring circuit impedance |
1MΩ | |
Measuring frequency range |
45~65 Hz | |
Overload capacity |
2 times rated value for 1 second | |
Measurement of input current |
CT secondary output |
Ratings: 1A/5A (default), 100mA/mV (optional) |
CT primary side range |
1~9999 A | |
Current measurement range |
0.003 ~ 6 A, rated 5A | |
Measuring circuit |
<0.01 ohm |
impedance | ||
Overload capacity |
20 times the maximum current for 0.5 seconds |
|
Auxiliary power supply |
Operating voltage range |
80~300 VAC / 100~420 VDC |
Operating Frequency Range |
45~65 Hz | |
Power consumption |
< 4VA/0.5W | |
Electrical Pulse Output |
Output method | Open collector optocoupler pulse |
Pulse constant | Can be set to: each pulse equal to 0.001, 0.01, 0.1, 1, 10, 100 kWh/kvarh |
|
Pulse width | Can be set to: 60, 100 (default), 200ms | |
Pulse output type |
Can be set to: forward/reverse/total active or reactive power |
|
Output level | Class A, reference standard IEC 62053-31 | |
Input Voltage | 5~27 VDC | |
Pulse indicator on the panel | The pulse constant is 5000 imp/kWh, representing the total active power on the secondary side |
|
Real-time clock timing accuracy | 0.5 s/d |