AT-MPM-S uses a 96mm panel mounted display and can be used in conjunction with our new "MultiClick" solution. It allows you to monitor 32 three-phase / 96 single-phase channels from a centralized point, eliminating the need for 32 separate panel meters. All MPM devices connected to the MPM bus can be configured through the human-machine interface. The series products are connected via RJ, without manual twisting of wires, saving construction time, facilitating installation, and being safe and reliable.
Main Features:
- Centralized monitoring of 32 three-phase/96single-phase channels.
- Human machine interface operation.
- No need for manual threading.
- Easy installation.
-
Safe and reliable.
Voltage/Current Input |
Rated Voltage |
L230 VAC(L-N)/400 VAC(L-L) |
CT Input |
100mV |
Voltage Input |
Measurement Range:85~276 VAC(L-N),85~480 VAC(L-L) |
Frequency |
45~65 Hz |
Overload Capacity |
2xRated Voltage by lasting 1s |
IP Class |
LCD display:IP51(Indoor); |
Installation |
TH35-7.iDIN Rail |
Flammability Class |
UL 94 V-0 |
Utilization Category |
UC2 |
Environment Specifications |
Operation Temperature |
-25~+55ºC |
Storage Temperature |
-40~+80ºC |
Humidity |
<90%,no condensing |
Vibration Frequency |
Range:10~150Hz,Refer to IEC 60068-2-6 |
Communication Specifications |
Interface and Protocol |
2-Wire RS485;Modbus RTU |
Baudrate |
1200,2400,4800,9600(Default),19200,38400 bps |
Parity |
None(Default),Even,Odd |
Stop Bit |
1(Default),2 |
Response Time |
<100ms |
Communication Terminals |
Wire Diameter:26~14 AWG;Torque:0.4 N.m(Max.) |
Temperature Rating of Connection Cable |
23ºC±2ºC |