Customization: | Available |
---|---|
After-sales Service: | 3 Years |
Warranty: | 3 Years |
Still deciding? Get samples of US$ 79/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Parameter | Value | |||
Applicable grid | Three-phase four-wire, three-phase three-wire, single two-wire, three-phase | |||
Working power | Voltage range | AC/DC85~265V | ||
Power consumption
|
≤5W | |||
Input | Voltage | Rated | AC100V,220V,400V | |
Overload | 1.2 times continuous, 2 times (10s) | |||
Power consumption | <0.4VA/Phase | |||
Impedance | ≥200kΩ | |||
Current | Primary current | 1-9999A | ||
Secondary input | 1A or 5A | |||
Short-time overcurrent | 20 times the maximum current for 0.5 seconds | |||
Power consumption | <0.2VA/Phase | |||
Impedance | ≥0.1Ω | |||
Output | Switching output | Relay output; can set any alarming power, default remote control | ||
Switching input | Dry contact input, photoelectric isolation | |||
Accuracy index | Voltage/current | 0.2% | ||
Frequency | 0.2% | |||
Power/power factor | 0.5% | |||
Active power | Class0.5S | |||
Reactive power | CLass1.0 | |||
Communication | Bus type | RS485 | ||
protocol | Modbus RTU | |||
Environment | Operation temperature | -25ºC~55ºC | ||
Storage temperature | -40ºC~70ºC | |||
Operating humidity | ≤90%RH, non-condensing, no corrosive air | |||
Storage humidity | ≤95%RH, non-condensing, no corrosive air | |||
Altitude | ≤2000m | |||
EMC electromagnetic compatibility test | Electrostatic discharge immunity test | GB/T 17626.2-2006:test level 4, test voltage 8kV | ||
RF electromagnetic field immunity test | GB/T 17626.3-2006:test level 3, test field strength of 10V / m | |||
Fast transient pulse group test | GB/T 17626.4-2008:test level 2, current voltage 1kV, other 500V | |||
Surge (shock) immunity test | GB/T 17626.5-2008:test level 4, test voltage 4kV | |||
RF field induction conducted harassment immunity test | GB/T 17626.6-2008:test level 3, test field strength of 10V / m | |||
Power frequency magnetic field immunity | IV Level (GB/T17626.8 IEC 61000-4-8) | |||
Oscillation wave immunity test | GB/T 17626.12-1998: test level 3 | |||
Electromagnetic emission limits | Qualified (GB/T14598.16 IEC 6255-25) | |||
Conformity to Standards | GBT22264.1-2008 Mounted digital display electrical measuring instrument Part 1: Definition and general requirements | |||
GBT22264.7-2008 Mounted digital display electrical measuring instrument Part 7: Special requirements for multifunctional instruments | ||||
GBT22264.8-2009 Mounted digital display electrical measuring instrument Part 8:Recommended test methods |