Rated parameters |
Working power supply |
AC/DC22V |
AC rated voltage (line voltage) |
400V |
AC rated current (external through-core current transformer) |
400A,300A,200A,150A,100A,75A,50A,25A,15A,10A,5A,1A |
Switch node input |
Incentives |
24V internal excitation |
Debounce time |
20ms |
Relay contact output capacity |
Normally closed relay |
AC400V / DC250V
Maximum current allowed to be disconnected: 10A
Long-term allowable closing current: 8A |
Normally open relay |
AC250V / DC30V
Maximum current allowed to be disconnected: 5A
Long-term allowable closing current: 5A |
AO Output |
Output range |
(4~20)mA |
Load capacity |
500Ω |
Voltage range |
12VDC~36VDC |
Power consumption |
AC voltage circuit |
>0.75VA/phase (Rated time) |
Device power circuit |
>6W |
Overload capacity |
AC current loop |
2 times rated current, continuous operation
10 times rated current, 10s allowed
40 times rated current, 1s allowed |
AC voltage circuit |
1.2 times rated current, continuous operation
1.4 times rated current, 10s allowed |
measurement accuracy |
Line voltage measurement range |
380V 10V~456V; Deviation: ±0.5%
690V 10V~828V; Deviation: ±0.5% |
Current measurement range |
(0.05~1.2) times rated current; Deviation: ±1.0% |
Active Power |
±1.0% |
Reactive power |
±2.0% |
Active energy |
±2.0% |
Reactive energy |
±2.0% |
Frequency |
±0.05HZ |
Power Factor |
±2.0% |
Analog output |
±2.0% |
Protection setting error |
Action Value |
|
Electric current |
±50mA or customized ±3% |
Voltage |
±2V or customized ±3% |
Action time |
|
Definite time |
Within the range of 0s~3s (including 3s), it shall not exceed 60ms.
Within the range of 3s~99.9s, it shall not exceed ±2% of the set value. |
Inverse time limit |
Within the range of 0s~3s (including 3s), it shall not exceed 100ms.
Within the range of 3s~99.9s, it shall not exceed 5% of the set value. |
Working environment |
Operating temperature |
-25ºC~55ºC |
Storage temperature |
-40ºC~70ºC |
Operating humidity |
≤90%RH No condensation, no corrosive gas location |
Storage humidity |
≤95%RH No condensation, no corrosive gas location |
Altitude |
≤2000m |
Electromagnetic compatibility performance |
Electrostatic discharge immunity |
IV Level (GB/T17626.2 IEC 61000-4-2) |
Radiated radio frequency electromagnetic field immunity |
III Level (GB/T17626.3 IEC 61000-4-3) |
Electrical fast transient burst immunity |
IV Level (GB/T17626.4 IEC 61000-4-4) |
Surge immunity |
IV Level (GB/T17626.5 IEC 61000-4-5) |
RF conducted immunity |
III Level (GB/T17626.6 IEC 61000-4-6) |
Power frequency magnetic field immunity |
IV Level (GB/T17626.8 IEC 61000-4-8) |
Oscillation wave immunity |
III Level (GB/T17626.12 IEC 61000-4-12) |
Electromagnetic emission limits |
Qualified (GB/T14598.16 IEC 6255-25) |
Electrical insulation performance |
Dielectric strength |
2kVPower frequency voltage, 1 min (GB/T13729) |
Insulation resistance |
Not less than 100MΩ (GB/T13729) |
Surge voltage |
5kV, 12/50μS (GB/T13729) |
Mechanical behavior |
Vibration response/durability |
I Level (GB/T11287) |
Shock response/durability |
I Level (GB/T14537) |
Collision Response |
I Level (GB/T14537) |